Back

Topic

[KB536]Modbus Plus Protocol

Tags: Cimway

13 years ago
By RM
Options
Print
Applies to:

PcVue version 10.0 (Build 2476)


Summary:

This article explains how to use Modbus Plus protocol with PcVue 10.0.


Details:

The Modbus Plus driver is not supplied with PcVue version 10.0 as support for the required hardware and software was suspended by the manufacturer, Schneider.
However this driver can be added manually to PcVue 10.0.

First step:

Download cwpModbusPlus.pdb and cwpModbusPlus.dll and copy manually to the BIN directory.

Second step:

Open protoc.dat file (Bin Directory) with a text editor and replace the line:

#PROTOCOL,026,10,CWMBP.DLL

  with

PROTOCOL,026,10,cwpModbusPlus.dll

You will find attached doc file protocol_mbp.doc describing protocol implementation.

Please note that this protocol needs an additional card, the SA85 (PCI Bus ref: 416NHM30030) and corresponding driver (MBX driver), to work. These items were originally suppled by Schneider.

Download attachments: 


Created on: 27 Dec 2011 Last update: 13 May 2024