Applies to:
PcVue all versions. |
||
|
||
Summary:
Using Modbus IP, in network architecture, its possible for the client station to unexpectedly communicate directly with equipment. How?
|
||
|
||
Details:
To prevent stations other than servers are able to communicate with equipment, you should add to all lines beginning with NETWORK in the file COMM.DAT, the name of a server list as shown below: BOARD,0,1,1,0,0,0,0,,,0,0,”” NETWORK,0,0,A14,211,,0,0,NO,0,0,0,25,0,1,0,0,,,0#0#0#0#0,LSREDONDANCE,,0,0,””,0,0,0,,,1 EQT,0,0,0,API_Y,3,SINEC-H1,1,0,0,0,0,20,0,1,0,,0,,1#0,0,,,0,0,”” FRAME,0,0,0,0,TC_Y,0,64,512,RW,1,DB ,1,0,0,1,0,11,1024#0,11,1,1,,,0,0,”” |
||
|
||
|
Created on: 17 Dec 2010 Last update: 13 May 2024