Back

Topic

[KB350]Migration of COMM.DAT to Pcvue version 7.0 onwards

Tags: Migration

14 years ago
By RM
Options
Print
Applies to:

PcVue 7.00c.


Summary:

Two new data types for Cimway, Bytes LM and Bytes ML, were introduced in Pcvue version 7.00beta9. These are to allow the possibilty of data inversiion. The previous data type, Byte I/O, is no longer recognised.


Details:

The solution is to open the COMM.DAT file with a text editor and replace any occurrences of Byte I/O with, Byte I / O LMsb, respecting the total of 15 characters of this field.


Created on: 30 Dec 2010 Last update: 13 May 2024