Back

Topic

[KB185]Messages 16718 and 16719: Write, %s, not connected OPC group

Tags: Error, Error ID, Error messages numbers

14 years ago
By RM
Options
Print
Applies to:

PcVue all versions.


Summary:

This article explains how to deal with error messages 16718 and 16719.


Details:

French PcVue: “16718, OPC, Ecriture, %s, Groupe OPC non connecté”
English PcVue: “16719, OPC,Write,%s, not connected OPC group”

%s is the name of the PcVue variable referenced by this message.

Explanation

You are trying to write to an item that is not available. The group or OPC server that includes the item of the variable specified in the message has not been launched.

In PcVue, check whether you have specified in the OPC server properties the option Active at launch.