Applies to:
PcVue version 9.0 onwards. |
||
|
||
Summary:
The number of variables allowed per project can be read in the VarConf.dat file at start-up or can be defined via a start-up option. |
||
|
||
Details:
Since PcVue version 9.0 the number of variables has been configurable. You can find it in the varconf.dat file, in the [VARIABLE] section: The format is as follows: [VARIABLE] The MaximumNumber property here contains the maximum number of variables allowed. By default it is 300000, while the maximum is of 1000000. Note: The option “-l xxx” on the command line for starting PcVue also lets you change the maximum number of variables to xxx. Obviously, you will need to have a Complete key to set the maximum limit. |
||
|
||
|
Created on: 02 Sep 2011 Last update: 13 May 2024