[KB625]How to optimize/increase communication speed with a PLC

Tags: Cimway, Equipment, PLC

12 years ago
By RM
Options
Print

Applies to:

PcVue all versions.


Summary:

How to improve communication when the status is e000.


Details:

A communication status of e000 means that frames are being scanned at a slower rate than has been configured.

One possible solution is to declare a second connection to the equipment (node) and distribute the frames across the two connections. Frames for the two connections are then processed in parallel potentially improving performance. The aim is to have a status of a000 (normal for a read/write frame).

The pre-requisite is that the PLC supports multiple connections from the master (PcVue).