[KB74]Floating point variables from the Eurotherm OPC Server

Tags: OPC, OPC-DA Server

14 years ago
By RM
Options
Print
Applies to:

PcVue version 7.00 onwards.
While the basic content of this article remains valid, details may have changed since it was written.


Summary:

This article describes how to retrieve analog values from a Eurotherm OPC server.


Details:

Eurotherm OPC Server converts analog values to string format. When you connect an OPC client you may encounter problems with interpreting floating point values, depending on the version of Windows OS.

In US versions of Windows, “.” is used as decimal point character but  in French version “,” is used

If you retain the default settings in a French version of Windows, a new error message (NS IEEE, added since version PcVue 7.20a) is displayed in the Variable Selector of  PcVue when an analog value is read.

Solution

There is a workaround for reading floating-point analog values correctly with the PcVue

OPC client installed on a French windows version. In your regional settings in the Windows Control Panel, change the decimal point character from “,” To “.”.


Created on: 15 Oct 2010 Last update: 13 May 2024