Topic
[KB169]Errors 172 and 173: Message ignored: %s
Tags: Error, Error ID, Error messages numbers
Applies to:
PcVue all versions. |
||
|
||
Summary:
This article explains how to deal with error messages 172 and 173. |
||
|
||
Details:
French PcVue: “172, Message ignored: %s” %s has the following form: t=%d, f=%d, l=%d, spc=%d, dpc=%d, s=%d, d=%d Possible explanations This message mostly appears in multistation configurations, when a thread from a station sends a message to a thread of another station. The thread indicated in parameters has not processed a message. As a result PcVue returns the message above in the Event Viewer. Possible cause The usual cause of this message is that your stations are not running the same PcVue version. Check the PcVue version on both stations. |
||
|
||
|
Created on: 19 Nov 2010 Last update: 13 May 2024