Details:
System.Bacnet.<network>.Status
Value |
Description |
0
|
Connected
|
1
|
Error: The device is not detected (for device, …). Inherited error for all children (notification, log, …).
|
2
|
Warning: At least one BACnet network interface is already in use by a third party tool (for network, …). Inherited error for all children (device, notification, log, …).
|
3
|
Error: Start stack has failed and the network has not started (for network, …). Inherited error for all children (device, notification, log, …).
|
System.Bacnet.<network>.<device>.Status
Value |
Description |
0
|
Connected
|
1
|
Error: The device is not detected (for device, …). Inherited from Network
|
2
|
Warning: At least one BACnet network interface is already in use by a third party tool. Inherited from Network
|
3
|
Error: Start stack has failed and the network has not started (for network, …). Inherited from Network
|
4
|
Error: another device uses the same device Id than the local device Id. Inherited error for all children (device, notification, log, …).
|
5
|
Warning: No or bad watchdog (BACnet object or property unknown), the state of device is uncertain (for device)
|
6
|
Warning: No watchdog or problem of create watchdog of notification, the state of notification is uncertain (for notification)
|
7
|
Warning of the subscription to the recipient-list of the notification-class. The device PcVue is not present in the recipient-list of the notification-class (for notification)
|
8
|
Warning of the subscription to the recipient-list of the notification-class. The notification-class instance exists but the register has failed (for notification)
|
9
|
Warning: The object instance is unknown in the device (for schedule, calendar, log, notification)
|
10
|
Error: conflict, 2 devices have the same device ID (for device, …). Inherited error for all children (notification, log, …)
|
11
|
Warning: deactivated, trial period elapsed
|
|