[KB507]ERROR Message 5002 : Variable unknown (x) from station y Manager User Interface Function Recipe
Applies to:
PcVue version 8.00 onwards. |
||
|
||
Summary:
This article give more details about error message 5002 |
||
|
||
Details:
The error message “5002 : Variable unknown (x) from station y Manager User Interface Function Recipe” appears when a wrong value in a DDE text variable is used in a recipe. The recipe is set with a DDE text variable to be copied to another variable. If the value of the DDE text variable contains the character “,” it is interpreted like a variable name separator by PcVue for DDE and the message appears. The x in the message is the value in the DDE text variable value just after the character “,” To fix the problem the character “,” must not be used in a DDE text variable used for a recipe copy.
|
||
|
||
|
Created on: 30 Sep 2011 Last update: 13 May 2024