Back

Topic

[KB507]ERROR Message 5002 : Variable unknown (x) from station y Manager User Interface Function Recipe

Tags: DDE Server

13 years ago
By f-flechearcinfo-com
Options
Print
Applies to:

PcVue version 8.00 onwards.


Summary:

This article give more details about error message 5002


Details:

The error message “5002 : Variable unknown (x) from station y Manager User Interface Function Recipe” appears when a wrong value in a DDE text variable is used in a recipe.

The recipe is set with a DDE text variable to be copied to another variable.

If the value of the DDE text variable contains the character “,” it is interpreted like a variable name separator by PcVue for DDE and the message appears.

The x in the message is the value in the DDE text variable value just after the character “,”

To fix the problem the character “,” must not be used in a DDE text variable used for a recipe copy.

 


Created on: 30 Sep 2011 Last update: 13 May 2024