Knowledge Base
Knowledge Base Audit and diagnostic Messages 16754 and 16755: Create, %s, The OPC server is not in the registry
Topic
[KB198]Messages 16754 and 16755: Create, %s, The OPC server is not in the registry
Tags: Error, Error ID, Error messages numbers
Applies to:
PcVue all versions. |
||
|
||
Summary:
This article explains how to deal with error messages 16754 and 16755. |
||
|
||
Details:
French PcVue: “16754, OPC, Création, %s, Le serveur OPC n’est pas dans la base de registre” English PcVue: “16755, OPC, Create, %s, The OPC server isn’t in the registry” %s is the Server alias in PcVue. Explanation When you create a new OPC server in PcVue, the Event Viewer will return the above message if you specify a server name that is not in the Windows Registry. Unless you have specified a wrong server name, this error message usually appears when you install your application on a different computer, and the OPC servers are not registered on this other computer. Solution Check that you have completed the Server name field in the OPC server properties dialog box with a correct OPC server name. Check that the OPC server is in the Windows Registry :
|
||
|
||
|
Created on: 19 Nov 2010 Last update: 13 May 2024