Knowledge Base
Knowledge Base Audit and diagnostic List full type=0 LinkEnd count=8192 max=8192 message
Topic
[KB1102]List full type=0 LinkEnd count=8192 max=8192 message
Tags: Error, Error ID, Error messages numbers, Scada Basic, Trace
Applies to:
PcVue all versions |
||
|
||
Symptom:
The Event Viewer shows the following looped message “List full type=0 LinkEnd count=8192 max=8192” and sometimes PcVue crashes. |
||
|
||
Details:
This is a specific case to illustrate Errors 44 and 45: list full %s kb article. Here, the number of Scada Basic functions in a queue is too high (more than 8192) for a specific Scada program. This behavior happens when: – Too much Event Actions have been triggered. – Some Cyclics Actions are configured with a too fast period. PcVue is not able to treat all the functions call and stackes it in a linked list limited to 8192. At the end, the list is full and then the message is prompted. |
||
|
||
|
Created on: 20 Jan 2021 Last update: 30 May 2024