Applies to:
PcVue 15.0 onwards |
||
|
||
Summary:
This article explain the differents steps to configure a LON project using IzoT and PcVue. |
||
|
||
Required hardware : – 1 LIP : Router – PcVue 15 onwards (With the adequate license) – Izot CT (With the adequate license) – 1 API at least – LINX (if possible) : Switch The configuration need to be done on : I- Configuration of the LIP: To configure the LIP there is two possibilities : 1- On LIP web interface : a- You need to define which LIP is the server (only one can be made as server on your architecture) b- Configure all address IP for other equipments such as : LINX, other LIP …, Add the IP address of the machine where IzoT CT is used NB : All the equipments need to have in state column a green check (be enable) 2- On Echelon Configuration Server : Declare the IP address of the machine where is used the IzoT CT and declare all the IP addresses of the equipments II- Configuration of the IZOT CT A- Installation Prerequisite: Installation of the commissioning Tool (CT) and the VISIO A.1- Configuration of VISIO After the installation of Visio. Before the first utilisation, you need for each users follow the steps below 1- Launch the option, then open Visio Options 2- Go to Trust Center -> Trust Center Settings -> Macro Settings -> Select : Enable All Macros 3- Go to: Visio Options -> Advanced -> File Locations… Insert the adequate folders (depend your installation), in case of default installation, insert this paths : My Shapes: C:\Users\XXXXXXX\Documents\My Shapes Drawings: C:\Users\Public\Documents\LonWorks\IzoT CT\Drawings Templates: C:\Program Files (x86)\LonWorks\LonMaker\Visio;1033\Solutions Stencils :C:\Program Files (x86)\LonWorks\LonMaker\Visio;1033\Solutions Help:C:\Program Files (x86)\LonWorks\LonMaker\Visio;1033\Help;1033\Solutions Add-ons: C:\Program Files (x86)\LonWorks\LonMaker;1033\Solutions XXXXXXX: Name of the user (You can find it on the file explorer) Example : A.2- Configuration of Network card After the installation of IZOT CT, you need to configure the Network card, follow the step described below B- Creat a new project a- To create a new project, you need to launch the Izot Commissioning Tool as Admin b- In Network Name : Write the name of your project, then select the path of your project in the Drawing Base Path, finaly select Create Network c- You can change the name and the localization of the project
NB : When you launch the installation of plugins (by pressing Finish), the validation window may open in the background, you need to validate it to complete the installation C- Start a project
Repeat the step B without registering the plug-in D- Configuration of a project After starting a new project using IZOT CT, the configuration will be done using Visio D.1- Insert the Equipment communicating with IP Address (LIP,LINX):
NB : To commissionne an equipment you need to be OnNet
To send the Service Pin:
D.2- Add API
Final result Plug-in : Right Click on your API -> Plug-ins-> Select the appropriate one (in case you have a Wago API launch TOPLON PRIO installed before) II- Configuration in PcVue 1- Create the LON network (connect to the LON DB). 2- Add a node (connect to the API ) NB: For the optimization see the LonWorks Optimization |
||
|
Created on: 11 Jan 2021 Last update: 04 Sep 2024