Applies to:
Any PcVue version |
||
|
||
Summary:
How to launch the native driver only on the server machines and not the clients. |
||
|
||
Details:
For native driver there is no way to specify the server list in the dialog box. In that case the driver is activated on all the stations defined in the multistation architecture. In order to avoid error messages in the event viewer and to open unecessary socket on client station, one can do so by editing the COMM.dat file manually and specify the list either at:
Please note that this feature is not yet implemented at the equipment level. For instance if the server list of your project is called LS_SERVERS then you must modify the COMM.DAT file as follow. Network level: VERSION,1,0 BOARD,0,1,1,0,0,0,0,,,0,0,”” NETWORK,0,0,K01_511,263,,0,0,NO,0,0,0,1,0,1,0,0,,,0#0#0#0#0,LS_SERVERS,,0,0,””,0,0,3,,,1 EQT,0,0,0,KMAIN52I,1,MODBUS_DEC,1,0,0,0,0,1,0,1,0,,0,,192#168#1#160#502#0#0#10#0#0#0,0,,,0,0,””,0 FRAME,0,0,0,0,A403845,3,80,20,RW,3845,Real I/O MLsb ,11,0,0,0,100,0,0#0#0#0#0,0,1,1,,,0,0,”” EQT,0,0,0,KMAIN53I,1,MODBUS_DEC,1,0,0,0,0,1,0,1,0,,0,,192#168#1#161#502#0#0#10#0#0#0,0,,,0,0,””,0 FRAME,0,0,0,0,A403845,3,80,20,RW,3845,Real I/O MLsb ,11,0,0,0,100,0,0#0#0#0#0,0,1,1,,,0,0,”” The equipment KMAIN52I and KMAIN53I will be activated on the stations that are included on the LS_SERVERS list.
|
||
|
||
|
Created on: 06 May 2015 Last update: 13 May 2024